Effectiveness of a counterflow heat exchanger

Fraction of the largest possible heat transfer that an ideal counterflow exchanger achieves, from its number of transfer units and the ratio of the two heat-capacity rates.

Ref
HTR-16
Rev
v1
Field
Heat Transfer
Result
ε

The effectiveness ε of a heat exchanger is the heat actually transferred divided by the maximum possible, set by the stream with the smaller heat-capacity rate. For counterflow, ε = [1 − e−NTU(1−Cr)]/[1 − Cre−NTU(1−Cr)], with NTU = UA/Cmin and Cr = Cmin/Cmax. When Cr = 1 the formula becomes ε = NTU/(1 + NTU). The result lies between 0 and 1.

Fraction of the largest possible heat transfer that an ideal counterflow exchanger achieves, from its number of transfer units and the ratio of the two heat-capacity rates. At equal heat-capacity rates the second form applies.

Calculator

Solve for
0.110
01
  • Parallel-flow effectiveness for the same NTU and Cr0.5179
  • Effectiveness when Cr = 0 (boiling or condensing)0.6321
  • Effectiveness at double the NTU0.7746

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Effectiveness () current value 0.5647
NTUNumber of transfer unitsKey driver
0.0930.997
CrHeat-capacity-rate ratio, Cmin/Cmax
0.50.632
  • An exchanger with NTU = 1 and Cr = 0.5 has an effectiveness of 0.565: it transfers 56.5 % of the thermodynamic maximum. A parallel-flow exchanger of the same size would only reach 0.518.
  • Doubling the area (NTU = 2) lifts the effectiveness to only about 0.775: the second half of the area buys much less than the first.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing ()Local stepChange in result
NTU Number of transfer units0.1 to 10 0.093010.99660.9036+10%+5.28 %
Cr Heat-capacity-rate ratio, Cmin/Cmax0 to 1 0.50.63210.1321+10%−1.18 %

Sweep of Number of transfer units

Number of transfer unitsEffectiveness
0.10.09301
1.3380.6556
2.5750.8399
3.8130.9197
5.050.9583
6.2870.978
7.5250.9883
8.7620.9937
100.9966

Sweep one variable

Effectiveness ()Hover, touch, or use the arrow keys on the chart
0.20.40.60.81 246810 Number of transfer units now 0.5647

Variables and how each one contributes

ε

Effectiveness

Result ·

What the equation gives you. Everything else feeds it.

NTU

Number of transfer units

· typical 0.1 to 10

The number of transfer units, UA/Cmin: a measure of the size of the exchanger relative to the flow. Raises the effectiveness, with diminishing returns: a larger exchanger improves performance but ever more slowly. Raising it by 0.25 (to 1.25) moves the result by +12.4 %, from 0.5647 to 0.6346.

Cr

Heat-capacity-rate ratio, Cmin/Cmax

· typical 0 to 1

The ratio of the smaller to the larger heat-capacity rate, between 0 (one stream condensing or boiling) and 1 (balanced). Lowers the effectiveness: with more balanced streams the temperature difference shrinks along the exchanger. Raising it by 0.05 (to 0.55) moves the result by −1.18 %, from 0.5647 to 0.5581.

Worked example with the values above

  1. Exponential term: e−NTU(1−Cr) = e−1 × 0.5 = 0.6065.
  2. Numerator 1 − 0.6065 = 0.3935; denominator 1 − 0.5 × 0.6065 = 0.6967.
  3. ε = 0.3935 / 0.6967 = 0.5647.

Assumptions and limits

  • A counterflow exchanger with constant overall coefficient and constant specific heats, and no heat loss to the surroundings.
  • Steady flow of both streams, with no phase change except when Cr = 0.

Common mistakes

  • Using it for a crossflow or shell-and-tube exchanger, which have different formulas.
  • Taking Cr as Cmax/Cmin, which is above 1.

Statistics and uncertainty

Heat-capacity rates carry the uncertainty of flow and specific-heat measurement (about 2 to 5 %), so Cr is known to a few per cent. The effectiveness is only weakly sensitive to Cr at low NTU but more so at high NTU.

Where it is used

  • Rating an exchanger when the outlet temperatures are unknown.
  • Comparing counterflow and parallel-flow performance for a given size.

Maths you need

  • Heat-capacity rate: mass flow times specific heat, in W/K
  • Maximum heat transfer: Cmin × the inlet temperature difference