Real power, single-phase AC

Real power drawn by an AC load, including power factor.

Ref
ELE-20
Rev
v1
Field
Electrical
Result
P [kW]

P1 in watts, Vrms and Irms RMS voltage and current, φ the phase angle between them. cos φ is the power factor.

Only the part of the current that is in step with the voltage does useful work. The power factor tells you what fraction of the volt-amps becomes real power.

Calculator

Solve for
kW
V
100480
A
1100
0.51
  • Apparent power S = VI2.3 kVA
  • Reactive power Q1.003 kvar

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Real power (kW) current value 2.07 kW
IrmsRMS currentKey driver
0.20720.7
VrmsRMS voltage
0.94.32
cos φPower factor
1.152.3
  • A low power factor means the supply must carry more current for the same real power, wasting cable and generator capacity.
  • Phase angle φ and power factor are linked by pf = cos φ; a power factor of 0.9 corresponds to about 25.8°.
  • Use RMS values. Peak values overstate power by a factor of two.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing (kW)Local stepChange in result
Irms RMS current1 to 100 A0.20720.720.49+10%+10 %
Vrms RMS voltage100 to 480 V0.94.323.42+10%+10 %
cos φ Power factor0.5 to 1 1.152.31.15+undefined%—

Sweep of Power factor

Power factorReal power (kW)
0.51.15
0.56251.294
0.6251.438
0.68751.581
0.751.725
0.81251.869
0.8752.013
0.93752.156
12.3

Sweep one variable

Real power (kW)Hover, touch, or use the arrow keys on the chart
1.21.41.61.822.2 0.50.60.70.80.91 Power factor now 2.07

Variables and how each one contributes

P

Real power

Result · kW

What the equation gives you. Everything else feeds it.

Vrms

RMS voltage

V · typical 100 to 480

RMS supply voltage. Directly proportional.

Irms

RMS current

A · typical 1 to 100

RMS line current. Directly proportional.

cos φ

Power factor

· typical 0.5 to 1

1 for a pure resistor, lower for motors and inductive loads. Directly proportional: improving power factor raises real power at the same current.

Worked example with the values above

  1. Apparent power: S = VI = 230 × 10 = 2,300 VA.
  2. Real power: P = S cos φ = 2,300 × 0.9 = 2,070 W.
  3. That is 2.07 kW.

Assumptions and limits

  • Sinusoidal voltage and current at the same frequency.
  • RMS quantities.
  • Single-phase supply.

Common mistakes

  • Using peak instead of RMS values.
  • Reading apparent power (VA) as real power (W).
  • Forgetting the power factor.

Statistics and uncertainty

Power factor is the least certain input: meters typically measure it to ±1–2%, but loads vary with their duty. Errors combine as δP/P ≈ √[(δV/V)² + (δI/I)² + (δpf/pf)²].

Where it is used

  • Generator and supply sizing.
  • Motor load calculations.
  • Energy bill estimation.