Real power, three-phase AC

Total power delivered by a balanced three-phase supply.

Ref
ELE-21
Rev
v1
Field
Electrical
Result
P3 [kW]

P3 total real power, VLL line-to-line RMS voltage, Iline RMS line current and φ the per-phase voltage–current angle. Balanced load.

Three-phase supplies deliver power through three conductors, with √3 times the line voltage and current combining for the total. It is the standard way to move large power efficiently.

Calculator

Solve for
kW
V
20011,000
A
1500
0.51
  • Apparent power √3 V I13.86 kVA
  • Phase voltage VLL/√3230.9 V

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Total real power (kW) current value 11.78 kW
VLLLine-to-line voltageKey driver
5.89324
IlineLine current
0.589294
cos φPower factor
6.9313.9
  • A 400 V three-phase supply carries the same power as a 230 V single-phase supply with less than half the current per conductor.
  • The √3 comes from the 120° spacing between phases, not from a loss.
  • The formula applies to star and delta connections as long as line quantities are used.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing (kW)Local stepChange in result
VLL Line-to-line voltage200 to 11,000 V5.889323.9318+10%+10 %
Iline Line current1 to 500 A0.5889294.4293.9+10%+10 %
cos φ Power factor0.5 to 1 6.92813.866.928+undefined%—

Sweep of Line current

Line current (A)Total real power (kW)
10.5889
2.1751.281
4.7292.785
10.286.056
22.3613.17
48.6228.63
105.762.27
229.9135.4
500294.4

Sweep one variable

Total real power (kW)Hover, touch, or use the arrow keys on the chart
050100150200250300 1520100500 Line current (A), log scale now 11.78

Variables and how each one contributes

P3

Total real power

Result · kW

What the equation gives you. Everything else feeds it.

VLL

Line-to-line voltage

V · typical 200 to 11,000

RMS voltage between any two lines (400 V is common). Directly proportional.

Iline

Line current

A · typical 1 to 500

RMS current in each line. Directly proportional.

cos φ

Power factor

· typical 0.5 to 1

Per-phase power factor. Directly proportional.

Worked example with the values above

  1. Apparent power: S = √3 × 400 × 20 = 13,860 VA.
  2. Real power: P = S cos φ = 13,860 × 0.85 = 11,780 W.
  3. That is 11.78 kW.

Assumptions and limits

  • Balanced three-phase load and supply.
  • Line-to-line voltage and line current (not phase values).
  • Sinusoidal steady state.

Common mistakes

  • Using phase voltage in place of line-to-line voltage.
  • Forgetting the √3.
  • Using peak values.

Statistics and uncertainty

Relative errors combine as δP/P ≈ √[(δV/V)² + (δI/I)² + (δpf/pf)²]. Unbalanced loads break the formula; the total must then be found phase by phase.

Where it is used

  • Generator and motor sizing.
  • Ship and shelter power distribution.
  • Radar and transmitter supplies.

Maths you need

  • Single-phase power: P = VI cos φ
  • Phasors: three phases 120° apart